Purity III layouts

Multiple layouts supported by default

3D Tempulog TFMS
facilities monitoring and alarm system

 

 

3D Tempulog TFMS

 

Tempulog TFMS Technical Specification

Tempulog TFMS Base Station Specifications   4 Channel Sensor Unit Specifications
Part Number TFMSBS   Part Number TFMSS
Number of channels 64   Number of channels 4, 2 Temperature/Humidity & 2 doors
Number of dual sensors 16   Temperature Probes PT100 Class A 4 wire
Maximum distance to sensor 250 meters   Temperature range -196C to +200°C
Built in remote alarm SMS, Email   Temperature accuracy +-0.3°C
Alarm relay contacts 500 mA/24 volts   Temperature resolution 0.01°C
Battery backup 12 hours rechargeable   Humidity range 0-100%
Visual alarm Ultra bright led   Humidity accuracy
+-2%
Audio alarm Internal buzzer   Door input Volt free relay contact
Server communication Ethernet & GPRS   Distance to Base-Station 250 meters
Power supply 9-15 volts DC 150 mA   Communication Bidirectional
Display Graphic LCD   Frequency 433 HMZ band
Input Joystick   Onboard memory 32000 readings
Mounting Wall mounted   Signal Strength Transmitted to TFMSBS
Weight 1.95Kg   Antenna ¼ wave, 170 mm
Dimension HWD 165x320x42mm
  Battery Lithium Battery 3.6 V
      Battery life time 3 years minimum
      Low battery alarm indicator
Flashing LED
      Low Battery alarm Transmitted to TFMSBS
      Housing standard IP65
      Mounting Wall mounted
      Weight 150g
      Dimension HWD 97x65x36mm